USER’S GUIDE
masterswitch vm
MasterSwitch VM
Unit Configuration
Item Definition
Name Name of the MasterSwitch VM unit (23 characters maximum)
Cold Start
Delay
The time that MasterSwitch VM delays applying power to outlets, after AC
power is applied to the MasterSwitch VM unit.
Overload
Warning
Threshold
The percentage of a full load that triggers an overload warning. The warning
causes the overcurrent alarm LED to flash green and sound the alarm (if the
overload audible alarm property is configured).
Overload
Outlet
Restrictions
Any overload conditions that will prevent outlets from turning on. The
following actions are available:
• None—Always allow outlets to be turned on.
• On Warning—Do not allow outlets to be turned on when the Overload
Warning Threshold has been exceeded.
• On Overload—Do not allow outlets to be turned on when the load exceeds
100%.
• On Overload Warning—Sounds the alarm when the load exceeds the
Overload Warning Threshold.
Note: A changed setting is not used until an event occurs again, e.g. if the
overload warning threshold is exceeded and then changed, no alarm sounds.
Overload
Audible
Alarm
Any overload conditions that causes the audible alarm to sound. If the alarm
sounds, you can use the mute button to turn off the alarm or you can clear the
alarm. Selecting Disabled will not clear the alarm. The following actions are
available:
• Disabled—Disables the audible alarm.
• On Overload—Sounds the alarm when the load exceeds 100%.
Low Current
Threshold
The threshold for load current below which an SNMP trap is generated.
Reboot
Duration
Longest reboot duration in the set of accessible outlets. To change this value,
you must modify the reboot duration of accessible outlets. Used by
Sequenced Reboot and Delayed Sequenced Reboot.