Specifications
Output
Symmetra
®
400 kW - 1600 kW 400 V
General Output Specifications
Input
General Input Specifications
Regulatory
Protection
Physical
Communication and Management
Environmental
Battery System
Part No. SY400K400H SY600K600H SY800K800H SY1000K1000H SY1200K1200H SY1400K1400H SY1600K1600H
Nominal Input Voltage 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V
Nominal Input Current (400V) 595 A 893 A 1191 A 1488 A 1849 A 2156 A 2464 A
Input Wiring L1, L2, L3, N, PE
Input Frequency (programmable) 50 Hz, ±0.5-8% (display set-up)
Input Power Factor ~1
I THD <5% at full load
Max. Short-Circuit Withstand 200 kA
Level (I
CW
)
Input Voltage Tolerance Utility
Operation ±15%
Input Voltage Tolerance Bypass ±10% standard ±4, 6, 8, 10% (programmable)
Backfeed Protection Built-in backfeed contactor
Power Range 400 kW/kVA 600 kW/kVA 800 kW/kVA 1000 kW/kVA 1200 kW/kVA 1400 kW/kVA 1600 kW/kVA
Nominal Output Voltage 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V 3x400/230 V
Nominal Output Current (400V) 577 A 866 A 1155 A 1443 A 1793 A 2091 A 2390 A
Output Voltage Distortion Max 3% linear load
Efficiency in Battery Operation >95%
Efficiency at Full Load (AC-AC) 97%
Output Wiring L1, L2, L3, N, PE
Load Power Factor 0.9 leading to 0.8 lagging without derating
Output Frequency Mains synchronized in normal operation, ± 0.1% Hz free-running
Overload Capacity Utility Operation 200% for 60 seconds, 125% for 10 minutes
Overload Capacity Battery Operation 150% for 30 seconds
V THD Max 3% linear load, max 5% non-linear load
Output Voltage Tolerance Sym. load (0-100%): ±1% static, ±5% after 2 ms and ±1% after 50 ms
Nominal battery voltage 2*384 V
End of discharge battery voltage 2*326 V
Max. battery current at end of
638 A 957 A 1277 A 1596 A 1917 A 2337 A 2556 A
discharge
Communication Interface Web / Network Interface
Control Panel Advanced 10” Color LCD Touch-Screen User Interface
Audible Alarm Audible and visible alarms prioritized by severity
Emergency Power Off (EPO) Yes
Emergency Module Off (EMO) Yes
Indicators and controls Self diagnosing with surveillance of fuses, fans, batteries, temperatures etc.
Dimensions (HxWxD) mm 2032x2114x1067 2032x2536x1067 2032x3716x1067 2032x4138x1067 2032x4646x1067 2032x5068x1067 2032x5490x1067
Weights (kg) 2500 3200 4270 5090 6310 7016 7722
Minimum clearance around UPS Top clearance 500 mm (200 mm in installations with IP21 Drip Cover). Front clearance 1000 mm.
Color Grey (NCS 2703-G85Y), Black (NCS S 9000-N)
Seismic anchoring Yes
Seismic zone No
Surge IEC-100-4-5, EN50091-2
Thermal Yes
Short Circuit Yes
Safety IEC60950 3rd edition, EN50091-1-1
EMC/EMI/RFI EN50091-2, IEC 62040-3
Approvals CE, ISO 9001, ISO 14001
Altitude (operating) 1000 m = 100% load; 1500 m = 95% load; 2000 m = 91% load; 2500 m = 86% load; 3000 m = 82% load
Operating Temperature 0-40° C
Storage Temperature –15-40° C
Operating Relative Humidity 0-95% non-condensing
Storage Relative Humidity 0-95% non-condensing
Operating Elevation (m) 0-1000 m
Storage Elevation (m) 0-15,000 m
Audible noise, nom max. at 1 m from 74 74 74 75 75 75 75
unit (dB(A))
Protection Class IP20 standard, IP21 optional