APC AP9606 Specifications Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
Chapter 2. APC hardware and software background 23
Figure 13. PowerChute PLUS event actions and UPS delays
2.4.2 PowerChute network shutdown
PowerChute network shutdown software provides graceful, unattended shutdown
of multiple computer systems (up to 50) over the network. It communicates
across the network with an APC UPS equipped with an AP9606 Web/SNMP
Management Card. A Web browser can be used to quickly and easily configure
individualized server shutdown settings.
UPS On Battery event
System Shutdown Starting event
Command File executed (after a
10-second delay)
Operating system shutdown starts
"S" issued to put the UPS in sleep mode
UPS enters sleep mode, powers outlets off
Low Battery Condition event
Battery depleted
UPS switches off completely
60 sec
on-battery delay
60 sec
shutdown delay
600 sec
turn-off delay
600 sec
Low battery
warning delay
Total run time available
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 95 96

Comments to this Manuals

No comments