74 Implementing UPS Configurations with Microsoft Cluster Server
1. In the PowerChute PLUS main window, select Configuration > Event
Actions.
2. In the Event Actions window, select the PowerChute PLUS Started event.
3. Select the RunCommand File checkbox and click Options. Insert the
following in the Command File field:
"C:\UPS_CMD\UPS.CMD" StartUp >> C:\UPS_CMD\LOG.TXT
You must also change the UPS.CMD command file at point 2. Start the cluster
Server. If the Cluster is already started at this moment, you get an error message
that the service already started. Then resume the node.
A.2.1.2 PowerChute 5.2.1
We have written this redpaper with PowerChute PLUS Version 5.2. V5.2.1 is now
available. This version varies somewhat from PowerChute PLUS Version 5.2. If
you use a newer version than V5.2, we recommend that you perform intensive
tests.
A.2.1.3 LOG.TXT
The output of the command file UPS.CMD will be written to
C:\UPS_CMD\LOG.TXT. It may be possible to make this output more useful and
more readable with some time or date commands in the UPS.CMD command file.
A.2.2 Windows 2000
A.2.2.1 ACPI or power management
If you install Windows 2000 on a new model of IBM PC server, Windows 2000 will
automatically install the power management. However, you now have a problem:
PowerChute PLUS shuts Windows 2000 down. After shutting down, Windows
2000 switches the system off. Then, the UPS powers off. As soon as the power
failure is resolved, the UPS puts power on the power outlets but the server will
not start because it was switched off before the UPS turned off the power.
In our opinion you use the function key to disable the power management
function of Windows 2000 during the textmode setup of Windows 2000.
A.2.2.2 The UPS.CMD command file
The UPS.CMD command file as described in this redpaper will not work in
Windows 2000. Instead, you should use UPS.CMD.W2K, rename this file to
UPS.CMD, and configure your UPS as described in this redpaper.
The changes are:
Enable the operating system shutdown function from PowerChute PLUS 5.2.1
The script checks which resources are owned by the node and sets them
offline or moves them
Some small changes for the cluster command tool.
A.2.2.3 DELAY3.EXE
You should use SLEEP.EXE found in the Windows 2000 Resource Kit. This
Microsoft tool works in the same way as DELAY3.EXE. The difference is the use
of resources. SLEEP.EXE does not need as much CPU time as DELAY3.EXE.