APC DX Service Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 62
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
Performance Specifications—Water Cooled
16 APC NetworkAIR™ FM-DX
Performance Specifications—Water Cooled
FM-DX FM 35 FM 50
ECONOMIZER -- NET COOLING CAPACITY DATA -- BTU/HR (kW) @ 45F (7.2C) EWT*
80F DB, 67F WB (26.7C DB, 19.4C WB) 50% RH
Total 185,000 (54.3) 264,000 (77.3)
Sensible 141,000 (41.3) 201,000 (58.9)
75F DB, 62.5F WB (23.9C DB, 16.9C WB) 50% RH
Total 149,000 (43.9) 211,000 (62.0)
Sensible 129,000 (37.9) 184,000 (53.9)
75F DB, 61F WB (23.9C DB, 16.1C WB) 45% RH
Total 146,000 (42.6) 205,000 (60.0)
Sensible 137,000 (40.3) 195,000 (57.3)
72F DB, 60F WB (22.2C DB, 15.5C WB) 50% RH
Total 131,000 (38.3) 183,000 (53.6)
Sensible** 120,000 (35.3) 170,000 (49.9)
72F DB, 58.6 WB (22.2D DB, 14.8C WB) 45% RH
Total 121,000 (35.6) 172,000 (50.6)
Sensible 121,000 (35.6) 172,000 (50.6)
70F DB, 58.5F WB (21.1C DB, 14.8C WB) 50% RH
Total 119,000 (34.6) 165,000 (48.6)
Sensible 113,000 (33.0) 159,000 (46.6)
70F DB, 57.2F WB (21.1C DB, 14.0C WB) 45% RH
Total 111,000 (32.6) 158,000 (46.3)
Sensible 111,000 (32.6) 158,000 (46.3)
COOLANT REQUIREMENTS
THR -- MBH (kW) 162,000 (47.6) 263,000 (77.0)
85 F (29.4 C) Water In -- GPM (L/s) 29.5 (1.9) 47.9 (3.0)
Pressure Drop -- PSI (kPa) 5.4 (37.2) 8.4 (57.9)
Pressure Drop w/Econ Coil -- PSI (kPa) 8.8 (60.7) 17.1 (117.9)
WATER REGULATING VALVES
Size -- 2 Way Ball Valve -- Inches, NPT (Cv)*** 1-1/2 (35) 1-1/2 (35)
Size -- 3 Way Ball Valve -- Inches, NPT (Cv)**** 1-1/2 (35) 1-1/2 (35)
AIR SYSTEM -- DIRECT DRIVE CENTRIFUGAL
Air Volume -- CFM (L/s) 6,000 (2,830) 9,000 (4,245)
Blower Motor -- HP (kW) 4 (3) 4 (3)
External Static Pressure -- inches of water (Pa) 0.5 (125) 0.5 (125)
Number of Blowers 2 2
COMPRESSOR -- TANDEM SCROLLS
EER 20.1 17.8
Quantity 2 (tandem) 2 (tandem)
Nominal HP (kW) 9.0 (6.71) 15.6 (ll.64)
EVAPORATOR COIL -- V FRAME, COPPER TUBE/ALUMINUM FIN
Face Area -- ft
2
(m
2
)
21 (1.95) 21 (1.95)
Rows Deep 3 3
Face Velocity -- FPM (m/s) 286 (1.45) 428 (2.17)
HUMIDIFICATION --- SOLID STATE ELECTRODE CANISTER
Flush Cycle automatic automatic
Capacity -- Lbs/hr (Kg/hr) 10 (4.53) 10 (4.53)
kW 3.2 3.2
FILTERS
Quantity 55
Size -- Inches (mm) 12.8×29.0 (325×737) 12.8×29.0 (325×737)
Depth -- Inches (mm) 4 (100.8) 4 (100.8)
REHEAT
Electric -- Equally Loaded Three (3) Phase, Finned Tubular, Low-Watt Density
Capacity -- BTU/HR (kW) Includes Motor Heat***** 40,000 (11.6) 47,000 (13.8)
PHYSICAL DATA
Weight -- lbs (kg)****** 1220 (553) 1350 (612)
Height -- Inches (mm) 76.89 (1,953) 76.89 (1,953)
Length -- Inches (mm) 70.87 (1,800) 70.87 (1,800)
Depth -- Inches (mm) 35.00 (889) 35.00 (889)
CONNECTION SIZES*******
Water In/Out -- Inches 1-1/2 1-1/2
Humidifier
Supply Line -- Inches 1/4 1/4
Condensate Drain
Drain Line -- Inches 1/2 1/2
MultiCool
Supply Line -- Inches 1-1/2 1-1/2
Return Line -- Inches 1-1/2 1-1/2
***2-Way Single Seated, 400 PSI W.W.P. max
****3-Way Single Seated, 400 PSI W.W.P. max
*****With equal loading on each phase, rated at 208-230V / 3-phase, 480V / 3-phase and 600V / 3-phase
******Add 150lbs (68kg) when Economizer or MultiCool option is selected
*******Connection sizes, not recommended piping sizes. All water/steam piping is nominal.
Page view 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 61 62

Comments to this Manuals

No comments