APC NetworkAIR™ FM-DX 19
Electrical Data
AIR COOLED
REHEAT Electric
HUMIDIFIER Electrode Canister - Steam
VOLTAGE 208 230 480 600
FM 35
OA-w/DX 59.7 58.4 27.8 23.0
OA-w/DX&MultiCool 61.1 59.6 28.4 23.5
MCA 92.0 92.0 40.6 33.9
MOP 100.0 100.0 50.0 35.0
FM 50
OA-w/DX 96.1 91.3 45.5 36.5
OA-w/DX&MultiCool 99.7 94.5 47.0 37.8
MCA 132.2 132.2 66.4 49.7
MOP 150.0 150.0 70.0 50.0
WATER COOLED
REHEAT Electric
HUMIDIFIER Electrode Canister - Steam
VOLTAGE 208 230 480 600
FM 35
OA-w/DX 56.6 55.6 26.0 21.6
OA-w/DX&MultiCool 58.0 56.8 26.6 22.1
MCA 92.0 92.0 46.0 33.9
MOP 100.0 100.0 50.0 35.0
FM 50
OA-w/DX 90.6 86.3 43.2 34.5
OA-w/DX&MultiCool 94.2 89.5 44.8 35.8
MCA 132.2 132.2 66.4 49.7
MOP 150.0 150.0 70.0 50.0
GLYCOL COOLED
REHEAT Electric
HUMIDIFIER Electrode Canister - Steam
VOLTAGE 208 230 480 600
FM 35
OA-w/DX 61.1 59.6 28.6 23.7
OA-w/DX&MultiCool 62.4 60.8 29.2 24.2
MCA 92.0 92.0 40.6 33.9
MOP 100.0 100.0 50.0 35.0
FM 50
OA-w/DX 98.3 93.3 46.2 37.3
OA-w/DX&MultiCool 101.9 96.5 47.8 38.6
MCA 132.2 132.2 66.4 49.7
MOP 150.0 150.0 70.0 50.0
OA = Operating Amps, MCA = Wire Size Amps, MOP = Maximum Overcurrent Protection
Locked Rotor Amps (LRA)
VOLTAGE FM 35 FM 50
208-230/3/60 123.0 195.0
480/3/60 49.5 95.0
600/3/60 40.0 80.0
* LRA data based on tandem compressors