32 APC NetworkAIR™ FM-DX
Fluid Coolers
*Fluid coolers can be selected for multiple indoor air conditioning units from the factory. Consult factory
for help configuring many-to-one or one-to-many glycol loops.
Glycol-cooled fluid cooler—performance/electrical data
OHE SKU
Voltage
Ambient
Temperature
40%
Ethylene
Glycol
@130F
Air Quantity Fan/Motor
Connect
-ion Size
(inches)
Weight
Glycol
Volume
Electrical Data
95F 105F
PD(ft)
@GPM
CFM L/s Qty HP RPM Lbs Kg Gal L FLA MCA MOP
ACFC75126 208-230/1/60
FM35 N/A 14.0@30 20,500 9,675 3 1/2 1075 (2) 2-1/8 550 250 10.2 37.7 11.7 12.7 15.0
ACFC75198 208-230/3/60
FM35 N/A 14.0@30 20,500 9,675 3 1/2 1140 (2) 2-1/8 550 250 10.2 37.7 7.8 8.5 15.0
ACFC75199 480/3/60
FM35 N/A 14.0@30 20,500 9,675 3 1/2 1140 (2) 2-1/8 550 250 10.2 37.7 3.9 4.2 15.0
ACFC75129 600/3/60
FM35 N/A 14.0@30 20,500 9,675 3 1/2 1140 (2) 2-1/8 550 250 10.2 37.7 3.1 3.4 15.0
ACFC75132 208-230/3/60
N/A FM35 7.4@25 21,900 10,336 2 1-1/2 1140 (2) 2-1/8 790 359 9.2 34.8 14.0 15.8 20.0
ACFC75133 480/3/60
N/A FM35 7.4@25 21,900 10,336 2 1-1/2 1140 (2) 2-1/8 790 359 9.2 34.8 7.0 7.9 15.0
ACFC75134 600/3/60
N/A FM35 7.4@25 21,900 10,336 2 1-1/2 1140 (2) 2-1/8 790 359 9.2 34.8 5.6 6.3 15.0
ACFC75202 208-230/3/60
FM50 N/A 4.6@30 34,800 16,424 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.1 21.0 22.8 25.0
ACFC75203 480/3/60
FM50 N/A 4.6@30 34,800 16,424 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.1 10.5 11.4 15.0
ACFC75143 600/3/60
FM50 N/A 4.6@30 34,800 16,424 3 1-1/2 1140 (2) 2-5/8 1190 540 13.0 49.1 8.4 9.1 15.0
ACFC75167 208-230/3/60
N/A FM50 4.8@40 43,900 20,718 4 1-1/2 1140 (2) 2-1/8 1620 735 18.5 70.0 28.0 29.8 35.0
ACFC75168 480/3/60
N/A FM50 4.8@40 43,900 20,718 4 1-1/2 1140 (2) 2-1/8 1620 735 18.5 70.0 14.0 14.9 15.0
ACFC75169 600/3/60
N/A FM50 4.8@40 43,900 20,718 4 1-1/2 1140 (2) 2-1/8 1620 735 18.5 70.0 11.2 11.9 15.0
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection
Low noise glycol-cooled fluid cooler—performance/electrical data
OHE SKU
Voltage
Ambient
Temperature
40%
Ethylene
Glycol
@130F
Air Quantity Fan/Motor
Connect
-ion Size
(inches)
Weight
Glycol
Volume
Electrical Data
95F 105F
PD(ft)
@GPM
CFM L/s Qty HP RPM Lbs Kg Gal L FLA MCA MOP
ACFC75155 208-230/3/60
FM35 N/A 10.7@25 18,500 8,731 3 1/2 540 2-5/8 1190 540 13.0 49.1 10.5 11.4 15.0
ACFC75156 480/3/60
FM35 N/A 10.7@25 18,500 8,731 3 1/2 540 2-5/8 1190 540 13.0 49.1 5.3 5.7 15.0
ACFC75158 208-230/3/60
N/A FM35 7.7@40 17,500 8,259 3 1/2 540 2-5/8 1210 550 13.0 49.1 10.5 11.4 15.0
ACFC75159 480/3/60
N/A FM35 7.7@40 17,500 8,259 3 1/2 540 2-5/8 1210 550 13.0 49.1 5.3 5.7 15.0
ACFC75161 208-230/3/60
FM50 N/A 6.1@30 24,600 11,610 4 1/2 540 2-5/8 2480 1125 16.7 63.1 14.0 14.9 15.0
ACFC75162 480/3/60
FM50 N/A 6.1@30 24,600 11,610 4 1/2 540 2-5/8 2480 1125 16.7 63.1 7.0 7.4 15.0
ACFC75164 208-230/3/60
N/A FM50 10.1@40 23,400 11,043 4 1/2 540 2-5/8 3150 1430 16.7 63.1 14.0 14.9 15.0
ACFC75165 480/3/60
N/A FM50 10.1@40 23,400 11,043 4 1/2 540 2-5/8 3150 1430 16.7 63.1 7.0 7.4 15.0
FLA = Full Load Amps
MCA = Minimum Circuit Amperes
MOP = Maximum Overcurrent Protection