Scalable Solution for Critical Environments
APC NetworkAIR™ FM-DX 3
Dedicated Dehumidification Cycle
A dedicated dehumidification cycle allows the system to increase latent capacity without overcooling, lowering the
requirement for reheat and humidification. This is accomplished by operating one compressor, isolating a portion of
the coil from the refrigerant flow and lowering the evaporator temperature when dehumidification is required. Two
compressor operation during dehumidification mode may be enabled through the microprocessor for humid environ-
ments where more latent capacity is required.
Demand Fighting
In rooms with multiple units, return temperature and humidity may vary a small percentage. This variance may result
in units operating in conflicting modes. For example, one unit may be dehumidifying while another, within close
proximity, is humidifying. This results in demand fighting and lower overall efficiency.
Cooling Coils
Distributor
Expansion Valve
Distributor
Flow Regulator
NORMAL COOLING MODE DEHUMIDIFICATION MODE
Solenoid Closed
Sub-Floor
Raised Floor
Heat Load
Heat Load
Cooling Units
73°F(23.9°C)/33%
70°F(21.0°C)/55%