PowerDeck shelves: Instructions
®
990-9070 Rev 1 Page 7 of 8 May 2001
4.2 DC Connection
The outputs from the rectifier modules are wired from the backplane PCBs and commoned together on busbars.
Connection is by two 8mm studs, pitched at 25.4mm, on each busbar. A suitable double hole lug is
recommended.
4.3 Signals Interface
The signals from each rectifier are connected via ribbon cables from each backplane PCB on to a common node
card inside the shelf. There are two external interface connectors on this card, one 20 way connector (PL6) for
use with the APC DM2000 power monitoring system, and a 26 way General Interface connector with a different
set of general purpose signals (PL5). These connectors are illustrated in figure 5.1 overleaf and their pin out is
given in table 4.2 below.
Customer connection to the General Interface PL5 should use connector type: polarised 26way female socket
connector with 2.54mm x 2.54mm pin centres and strain relief e.g. Thomas & Betts part number 636-2641.
DM2000 interface PL6 General Interface PL5
PL6
pin
Signal Type PL10
pin
Signal Type
1 Fan fail IOC output 1 One or more rectifiers in fan fail IOC output
2 Overtemperature IOC output 2 One or more rectifiers in standby IOC output
3 Thermal Control IOC output
3 One or more rectifiers in
overtemperature
IOC output
4 Overvoltage IOC output
4 One or more rectifiers in thermal
control
IOC output
5 Current Limit IOC output 5 One or more rectifiers in overvoltage IOC output
6 Signals common 6 One or more rectifiers in current limit IOC output
7 Rectifier 1 fail Relay N/O 7 One or more rectifiers output healthy IOC output
8 Rectifier 2 fail Relay N/O 8 One or more rectifiers input healthy IOC output
9 Rectifier 3 fail Relay N/O 9 One or more rectifiers Iout > 15% IOC output
10 Rectifier 4 fail Relay N/O 10 Signals common
11 No connection 11 One or more rectifiers failed (0V=fail) Relay
12 Negative sense 12 Current share Control buss
13 Current Share Control buss 13 Voltage trim Control buss
14 Voltage trim Control buss 14 Remote shutdown (+ve) Opto input
15 Remote shutdown Opto input 15 Negative sense
16 Rectifier 1 current signal 5.1k source 16 Current Monitor (summed 0.01V/amp) 5.1k source
17 Rectifier 2 current signal 5.1k source 17 Positive sense
18 Rectifier 3 current signal 5.1k source 18 Auxiliary supply +10V
19 Rectifier 4 current signal 5.1k source 19 Post Mate Enable
20 No connection 20 Programme Down (Battery Test) Opto input
21 Set boost Opto input
22 One or more rectifiers in boost IOC output
23 Current Limit Program
24 Not connected
25 Not connected
26 Not connected
Note 1: IOC output = isolated open collector output
Note 2: Signals common (PL6 pin 6, PL10 pin 10) = return for all IOC signals, relay contacts, opto inputs and auxiliary supply.
See information about jumper J2 below.
Table 4.2