5.4 Cold Start
When the UPS is off and there is no utility power, it is possible to cold start the UPS to apply power to the
loads from the UPS’s battery.
PrPr
PrPr
Pr
essess
essess
ess and
hold hold
hold hold
hold the on/off button until the UPS beeps twice (about two seconds).
RR
RR
R
eleaseelease
eleaseelease
elease the on/off button to start the UPS.
Note:Note:
Note:Note:
Note: Cold start is not a normal operating condition. On-battery and low battery alarms work as described
in section 6.
6. Alarms
6.1 On Battery
In on-battery operation, the on-battery LED illuminates and the UPS sounds an audible alarm consisting of
four beeps every 30 seconds. The alarm stops when the UPS returns to on-line operation.
6.2 Overload
When the UPS is overloaded (i. e., when the connected loads exceed maximum listed in section 12) the
overload LED illuminates and the UPS emits a sustained tone. The alarm remains on until the overload is
removed. Disconnect nonessential load equipment from the UPS to eliminate the overload. The UPS tests
for overloads when operating on-battery and when performing self-tests.
6.3 Replace Battery
If the battery fails a self test, the UPS emits short beeps for one minute and the Replace Battery LED illumi-
nates. The UPS repeats the alarm every five hours. After one week, the alarm becomes continuous. Perform
the self-test procedure in Section 5.2 to confirm replace battery conditions. The alarm stops when the bat-
tery passes the self-test.
6.4 Low Battery
On-battery, when the energy reserve of the battery runs low, the UPS beeps continuously until the UPS
shuts down from battery exhaustion or returns to on-line operation.
7. Options
7.1 Interface kits
For computer systems that have built-in UPS monitoring features, a series of interface kits are available to
connect the UPS to your system. Each kit includes the appropriate interface cable to convert the UPS status
signals into signals your system recognizes (use only factory supplied or authorized UPS monitoring
cables). See your dealer or call the number at the front of this manual for more information.