OperationProcedures
ShutDownaSingleUPS
TheUPSremainsenergizedunlessitisshutdown.
1.Pressabuttontoexitsleepmode.
2.PresstheOFFbutton(A)for3seconds.
TheloadisnolongerprotectedbytheUPS.
Itissuppliedviathebypass.
3.Setthebatterycircuitbreakeroftheauxiliary
cabinetstoOFF.
4.SettheinputswitchQ1(B)toOFF.
Thechargernolongeroperatestokeepthe
batteriesfullycharged.
5.Opentheupstreamcircuitbreakersofthe
NormalACsourceandBypassACsourceto
completelypowerofftheUPS.
990-5219-001
MGEGalaxy500040-130kV A480V
11
Comments to this Manuals