11Smart-UPS On-Line SRT5K/6K Tower/Rack-Mount 3U/4U
Wiring Specifications
CAUTION
DAMAGE TO EQUIPMENT OR PERSONNEL
Adhere to all national and local electrical codes.
Wiring should be performed by a qualified electrician.
Strain reliefs are not provided with this unit. Snap-In strain reliefs are recommended.
Refer to the Installation Guide for knockout panel sizes.
The UPS must be wired into a branch circuit, equipped with a circuit breaker rated as specified in the tables below.
Actual wire size must comply with required amp capacity and national and local electrical codes.
Recommended input terminal screw torque: 16 lbf-in (2 Nm).
Failure to follow these instructions can result in equipment damage and minor or moderate injury
SRT5K/6KXLT, SRT5K/6KXLT-IEC models
Input connections Wire to L1, L2,
Output connections Wire to L1, L2,
System Wiring Voltage Current full
load, nominal
External input
circuit breaker,
(typical)
Wire size,
typical
SRT5KXLT
SRT5KRMXLT
SRT5KXLT-IEC
SRT5KRMXLT-IEC
Input
Output
208/240 Vac 24 A 30 A/2-pole Not applicable
SRT6KXLT
SRT6KRMXLT
SRT6KXLT-IEC
SRT6KRMXLT-IEC
Input
Output
208/240 Vac
33 A
29 A
50 A/2-pole 6 AWG
SRT5KXLI/SRT6KXLI models
Input connections Single phase: Wire to L, N,
Output connections Wire to L, N
System Wiring Voltage Current full
load, nominal
External input
circuit breaker,
(typical)
Wire size,
typical
SRT5KXLI
SRT5KRMXLI
Input
Output
220/230/240 Vac 24 A 40 A/2-pole 10 mm
2
SRT6KXLI
SRT6KRMXLI
Input
220/230/240 Vac
32 A
50 A/2-pole 16 mm
2
Output 28 A