2 Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual
Specifications
Specifications
NOTE: The model and serial numbers are located on a small, rear panel label. For some models, an additional label
is located on the chassis under the front bezel.
Hardware
8
pan head screws for securing rail cleats to UPS
8
pan head locking screws for securing rack-mount brackets/stabilizer brackets to the
UPS
1
pan head locking screw (black) for securing top covers to UPS
8
ornamental screws for securing UPS to rack
4
cage nuts for rack installation
2
rack-mount brackets for rack-mount configuration
stabilizer brackets for tower configuration
2
rail cleats
Temperature
Operating
Storage
32
° to 104° F (0° to 40° C)
5
° to 86° F (-15° to 30° C) charge the UPS battery every six
months
86° to 113° F (30° to 45° C) charge the UPS battery every three
months
This unit is intended for indoor
use only. Select a location sturdy
enough to handle the weight.
Do not operate the UPS where
there is excessive dust or the
temperature or humidity are
outside the specified limits.
Environmental factors impact
battery life. High temperatures,
poor utility power, and frequent,
short duration discharges will
shorten battery life.
Maximum
Elevation
Operating
Storage
6562 ft (2,000 m)
50,000 ft (15,240 m)
Humidity 0 to 95% relative humidity, non-condensing
Weight 215 lbs (98 kg) with battery module
107 lbs (49 kg) without battery module
27 lbs (12 kg) each battery module
215 lbs (98 kg)