14UPS Network Management Card 2 User’s Guide
Controlling UPS and Security
The Control menu options enable you to take immediate actions affecting your UPS and your outlets, and they
also have some security and network functions. These options can apply to individual UPS devices and a
Synchronized Control Group (SCG), if enabled, see “Synchronized Control of your UPS devices”.
This option is not available for all UPS devices.
See the following sections:
“UPS on Control menu”
“Outlet Groups on Control menu”
“Security on Control menu”
“Network on Control menu”
UPS on Control menu
Path: Control > UPS
This option applies to individual UPS devices and, for Smart-UPS only, a Synchronized Control Group (SCG),
see “Synchronized Control of your UPS devices”.
When you choose a radio button option and click Next, another screen summarizes the action to take place;
click Apply there to continue with the action.
The actions vary depending on whether you have a UPS device with Outlet Groups or not. The two tables
below cover these separately.
“Actions on the UPS screen for devices WITH Outlet Groups”.
“Actions on the UPS screen for devices with NO Outlet Groups”.
This has information on CLI options.
These screen check box options directly below apply to both tables.
CheckBox Description
Signal
PowerChute
Network
Shutdown Clients
This is greyed out if no PowerChute clients exist (see “PowerChute Network Shutdown
clients”).
Select this option to notify all servers configured as PowerChute Network Shutdown clients
that are in communication with this UPS to shut down according to the values configured for
PowerChute Network Shutdown Parameters (see “Shutdown on Configuration menu”).
However, this option will not notify servers when performing any bypass control actions.
Skip outlet off
delays
Turn off outlets immediately, skipping the configured outlet group delays.
You might want to do this in an emergency or to save runtime. Or the load devices might
already have been turn off manually.
Apply to Sync
Group
This only displays if synchronized control is enabled. See “Synchronized Control of your UPS
devices”.
See individual descriptions of the fields in the two tables below.