24UPS Network Management Card 2 User’s Guide
The End of Shutdown options enable you to set a condition and a delay time for when a UPS can turn back on
after AC utility power is restored. You can specify a Minimum Battery Capacity before the UPS will turn
back on. Set another pause, if necessary, before turning on with Return Delay.
Shutdown delays and forcing negotiations. A shutdown time for the UPS is calculated differently for a
UPS device with NO outlet groups compared to a UPS with outlet groups.
1. For a UPS with NO outlet groups, the shutdown time is the Maximum Required Delay value on the
NMC Shutdown screen plus 2 minutes plus the shutdown delay for the UPS.
2. For a UPS WITH outlet groups, the shutdown time is the Power Off Delay value on the NMC Outlet
Groups screen, see “Outlet Groups on Configuration menu”. (Not available with all UPS devices).
Note that devices with the prefix SUM behave like #1 above, not #2.
For both types of UPS, the shutdown time is negotiated by the NMC interacting with PowerChute Network
Shutdown (PCNS).
Use the Force Negotiation option (Configuration - Shutdown) to re-gauge the time when you change or add
a PCNS client. When you force a negotiation, the procedure is automatic; the details are discussed below.
PCNS starts with the NMC Low Battery Duration value, compares it to its own shutdown time and, if the
battery duration time is too low, tells the NMC to increase the values in #1 and #2 below to the
PCNS
SHUTDOWN REQUIRED TIME* plus 70 sec.
1. With NO outlet groups, the Maximum Required Delay.
UPS with NO outlet groups: shutdown time
UPS shutdown time
Max. Required Delay
(NMC Shutdown screen)
2 min
UPS shutdown delay
UPS WITH outlet groups: shutdown time
UPS shutdown time
Power Off Delay
(NMC Outlet Groups screen)
Force Negotiation: UPS with NO outlet groups
IF THEN
PCNS
Req. Shutdown
Time
NMC
Low Battery Duration
Max. Req. Delay
for the PCNS is
increased
to equal
PCNS
Req. Shutdown
Time
sec