15UPS Network Management Card 2 User’s Guide
For more information about the delays and settings, see “Shutdown on Configuration menu”,
“Synchronized Control of your UPS devices”, and “Outlet Groups on Control menu”.
ActionsontheUPSscreenfordevicesWITHOutletGroups
Action Description
Reboot UPS
Outlet Groups
Applies a Shutdown Immediately, AC Restart command to all outlet groups (see “Outlet
Groups on Control menu”). Click Next to see specific details on timing and delays.
Turns off the output power of the Switched Outlet Groups and then, if present, the Main Outlet
Group. Any outlet group to which the action is applied waits the number of seconds configured
for its “Reboot Duration” and “Power On Delay”. (Then, the outlet groups turn on if AC utility
power is available, or waits to turn on until AC utility power is available. See “What are Outlet
Groups?”).
If the UPS is in a Synchronized Control Group (SCG), select Yes or No for Apply to Sync
Group to choose whether to reboot all enabled members of the group. The UPS waits the
number of seconds configured for its Shutdown Delay and Return Delay, then turns on if AC
utility power is available, or waits to turn on until AC utility power is available.
Turn On UPS
Outlet Groups
Turns on the Main Outlet Group, if present, and then all Switched Outlet Groups. This option
displays only if the UPS is currently turned off. Click Next to see specific details timing and
delays.
If the UPS is in a Synchronized Control Group, select Yes or No for Apply to Sync Group to
choose whether to turn on all enabled members of the group. The UPS and outlet groups wait
the time configured for “Return Delay”, then turn on.
Turn Off UPS
Outlet Groups
Turns off the output power of the Switched Outlet Groups and then, if present, the Main Outlet
Group. Any outlet group to which the action is applied remains off until you turn on its power
again. Click Next to see specific details on timing and delays
If the UPS is in a Synchronized Control Group, select Yes or No for Apply to Sync Group to
choose whether to turn off all enabled members of the group.
Put UPS Outlet
Groups to Sleep
Puts the UPS outlet groups into sleep mode by turning off the output power of the UPS for a
period of time defined by the following parameters. Click Next to see specific details on timing
and delays
The outlet groups wait the times configured as their “Power Off Delay” before turning off
their power.
When input power returns, the UPS turns on output power after two configured periods of
time elapse: “Sleep Time” and “Power On Delay”.
If the UPS is in a Synchronized Control Group, select Yes or No for Apply to Sync Group to
choose whether to put all enabled members of the group into sleep mode. The NMC of the UPS
initiating the action waits up to the number of seconds configured as “Power Synchronized
Delay” for enabled group members to regain input power before it starts the “Return Delay”.
The UPS waits the number of seconds configured for its “Shutdown Delay”, then turns off.
After the hours configured as “Sleep Time” elapse, the UPS waits the number of seconds
configured for its “Return Delay”, then turns on if AC utility power is available, or waits to turn
on until AC utility power is available.