APC AP9630 User's Guide Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 85
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
32UPS Network Management Card 2 User’s Guide
This displays the name, alarm status, temperature, and humidity (if supported) for each sensor. Click the name
of a sensor to edit the name and location and to configure its thresholds and its hysteresis.
Thresholds. For each sensor, you set the thresholds for temperature and (if supported) humidity measured at
the sensor. When a threshold is breached, the alarm signals.
High and Low are warning messages. Maximum and Minimum are critical, they must be dealt with.
Hysteresis. Use the Hysteresis value to avoid getting alarms repeatedly for the same violation of the
temperature or humidity threshold.
When the temperature or humidity that causes a violation tends to waver slightly up and down, it can
repeatedly trigger the alarm. A greater hysteresis value can prevent this.
If the hysteresis value is not great enough, the wavering can first cause a threshold violation and then clear it,
meaning the alarm can be triggered several times. See the examples below, after noting the following.
For maximum and high threshold violations, the clearing point for the alarm is the threshold minus the
hysteresis value you input.
For minimum and low threshold violations, the clearing point is the threshold plus the hysteresis value.
Example of rising but wavering humidity: Say the maximum humidity threshold is 65%, and the humidity
hysteresis is 10%. Then, the humidity rises above 65%, causing an alarm. It then wavers down to 60% and up
to 70% repeatedly, but
because of the 10% hysteresis value the alarm is not cleared and therefore no
new alarm occurs. For the existing alarm to clear, the humidity would have to drop below 55% (which is 65%
minus 10%).
Example of falling but wavering temperature: Say the minimum temperature threshold is 12°C, and the
temperature hysteresis is 2°C. Then the temperature drops below 12°C, causing an alarm. It then wavers back
up to 13°C and then down to 11°C repeatedly, but
because of the 2°C hysteresis value the alarm is not
cleared and therefore no new alarm occurs. For the existing alarm to clear, the temperature would have to rise
above 14°C (which is 12°C plus 2°C).
Input Contacts screen
Path: Universal I/O > Input Contacts
Input Contacts displays the name, alarm status, and state (open or closed) of each contact. These are
automatically found and displayed here when you install the environmental accessory.
Click the name of an input contact for detailed status or to configure its values. When disabled, the contact
generates no alarm even when it is in the abnormal position. Other fields are discussed below:
Output Relay screen
Path: Universal I/O > Output Relay
Field Description
Alarm Status
Normal if this input contact is not reporting an alarm, or the severity of the alarm if this input
contact is reporting an alarm. If not enabled for a contact, it displays Disabled.
State The present state of this input contact: Closed or Open.
Normal State The normal (non-alarm) state of this input contact: Closed or Open.
Severity
The severity of the alarm that the abnormal state of this input contact generates:
Warning or Critical.
Page view 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 84 85

Comments to this Manuals

No comments