APC MGETM GALAXYTM 6000 User Manual Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
6739381EN/
Example of an installation comprising three modular UPSs with an external maintenance bypass (from 250 to 500 kVA)
Fig. 15
mains 1
earth
static
switch
inverter 1
rectifier
charger
Q4S
modular UPS cubicle 2
+
-
+
-
QF1
Q1 Q5N
Q4S
modular UPS cubicle 1
+
-
+
-
QF1
Q1 Q5N
Q4S
modular UPS cubicle 3
+
-
+
-
QF1
Q1 Q5N
Q3BP
Q5N
External maintenance bypass cubicle
External
maintenance
bypass line
mains 1
earth
static
switch
inverter 2
rectifier
charger
mains 1
earth
static
switch
inverter 3
rectifier
charger
load
mains 2
battery cubicle
beside rectifier-
inverter cubicle 1
other battery
cubicles (if
applicable)
earth
earth
frames interconnection for earthing
frames interconnection for earthing
mains 2
battery cubicle
beside rectifier-
inverter cubicle 2
other battery
cubicles (if
applicable)
earth
earth
frames interconnection for earthing
frames interconnection for earthing
mains 2
battery cubicle
beside rectifier-
inverter cubicle 3
other battery
cubicles (if
applicable)
earth
earth
frames interconnection for earthing
Important. The power cables between
each UPS and the upstream
protection devices must be the same
length. The same holds for the power
cables between each UPS cubicle and
the external maintenance bypass.
Installation (cont.)
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 45 46