APC MGETM GALAXYTM 6000 User Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
6739381EN/
1200kVA Static Switch Cubicle
cross-section AA
front view
Cables connected by lugs to 80 x 8 mm
copper terminals and 14 mm diameter
holes.
Height of connections relative to floor:
mains 2: 1310 mm;
inverter outputs: 550 mm;
load: 850 mm;
remote relay board: 570 mm max.
rearfront
mains 2
earth bar
trough (if applicable)
load
UPS
outputs
power cable routing via the bottom
power cable routing via the top
A
XR7
XR6
XR5
XR9
Q3BP
Q5N
XR8
card
cage
A
XR1
XR2
XR3
XR4
Q4S
on
off
on
off
on
off
static switch
bypass switch K2S
NL1L2L3
mains 2
NL1L2L3
load
ACPZ
board
XM
127
to
132
static
switch
NL1L2L3
UPS
outputs
additional relay
board (optional)
remote relay
board
earth bar
spacing uprights
spacing uprights
connection
from below
Installation (cont.)