Rectifier-inverter cubicles
Characteristics of rectifier-inverter cubicles
rated cubicle cubicle cubicle maximum
inverter width W height H depth D weight
output in mm (1) in mm in mm in kg
in kVA
250 1600 1900 ± 10 840 1650
300 1600 1900 ± 10 840 1650
400 1600 1900 ± 10 840 2030
450 1600 2000 ± 10 840 2070
500 1600 2000 ± 10 840 2205
600 3600 1900 ± 10 840 3500
Characteristics of Static Switch Cubicles
rated cubicle cubicle cubicle maximum heat
SSC width W height H depth D weight losses (2)
output in mm (1) in mm in mm in kg
in kVA in kW in cal./s
500 1000 1900 ± 10 840 350 2.9 696
800 1000 1900 ± 10 840 500 3.7 888
1200 1600 1900 ± 10 840 1000 < 0.5 < 120
2000 2450 1900 ± 10 840 1710 < 0.5 < 120
Static Switch cubicles
The parameters given in the table
opposite can be used to determine the
required rating of a single-unit or
modular UPS, a frequency converter, or
a parallel UPS with SSC.
Characteristics of external maintenance bypass cubicles
(Modular UPS with external maintenance bypass)
rated cubicle cubicle cubicle maximum
bypass width W height H depth D weight
in kVA in mm (1) in mm in mm in kg
1200 1200 1900 ± 10 840 450
External maintenance bypass cubicles
Characteristics (cont.)
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.
"Pack Advance" cubicles
Characteristics of "Pack Advance"Cubicles
rated cubicle cubicle cubicle maximum heat
SSC width W height H depth D weight losses (2)
output in mm (1) in mm in mm in kg
in kVA in kW in cal./s
300 400 1900 ± 10 840 335 2.9 696
400 400 1900 ± 10 840 440 3.7 888
450 400 1900 ± 10 840 440 < 0.5 < 120
(1) 25 mm must be added on each side to the indicated cubicle width, i.e. 50 mm in all per cubicle. This
applies to all cubicle installation cases.
When installing several cubicles, allow for a tolerance of 0/+3mm per metre.