Page view 23
Page 24 - 6739381EN/JD
Battery cubicle (example of cubicle containing battery circuit breaker QF1)
cross-section AA
front view
This battery cubicle shown is an
example only, given that characteristics
of these cubicles vary greatly from one
cubicle to another:
remove the terminal shield from the
battery circuit breaker QF1 to make the
connections to this circuit breaker;
in the case of installations having
several battery cubicles, the
connections to be made between
cubicles are indi-cated in the
instructions accompanying the cubicles
(or in the drawing file for sophisticated
installations);
Note:
The optional "Temperature Monitor"
unit is located at the top of the left-hand
door in one of the battery cubicles.
Cubicles not containing a battery circuit
breaker have an additional row of cells
at the bottom.
Important note:
the cubicle is supplied with a fixture
locking circuit breaker QF1 in the open
position. Do not remove this fixture
before first startup: accidental closing
of QF1 will power up the downstream
circuits which could be hazardous for
personnel and permanently damage
the battery by deep discharge;
connections between battery
cubicles should be made in compliance
with applicable regulations: take all
protective measures associated with
working on live equipment and in
particular use only qualified personnel
equipped with gloves, protective
goggles, insulated tools, etc.
Connection of cables through lugs to
copper terminals
power cable routing via the bottom
cables tied
to the circuit
breaker
support or to
the grating
rear
connection
from below
trough (if
applicable)
front
A
A
QF1
+
+
auxiliary
connection
terminal
block XR1
to battery
cells
fixture for locking circuit breaker
QF1 in open position
(to be left in place until first UPS startup)
spacing
uprights
spacing
uprights
cables tied to circuit
breaker support
to inverter-
rectifier
cubicle
cubicle
earthing
on terminal
or on the
grating
Installation (cont.)