APC MGETM GALAXYTM 6000 User Manual Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
Page 20 - 6739381EN/JD
Installation (cont.)
500kVA modular UPS rectifier-inverter cubicle
cross-section AA
front view
Height of connections relative to floor:
mains 1: 450 mm ;
mains 2 and load: 337 mm ;
battery: 385 mm ;
remote relay board:
1030 mm.
Cables connect by lugs:
mains 1:
to 50 X 10 mm copper terminals and
12,6 mm diameter holes, and gudgeon
10 mm diameter;
mains 2 and load:
to 50 X 8 mm copper terminals and 5
holes of 12,6 mm diameter;
battery:
to 80 X 8 mm copper terminals and 2
holes of 12,6 mm diameter.
A
A
L1 L2 L3N
load
Q5N
XR7
XR6
XR5
XR9
XR8
XR3
XR4
XR2
XR1
Q3BP
Q4S
L1L2 L3N
mains 2
"ACOZ" board
"FHCZ"
board
on
off
on
off
on
off
on
off
Q1
L1L2 L3
mains 1
"INTZ"
board
"MISI" board
XM7
XM5
XM6
XM12
XM10
XM11
L+ L
battery
static
switch
rectifier
charger
inverter
stack
additional remote
relay board (optional)
card
cage
remote relay
board
spacing
uprights
spacing
uprights
air extraction
air admission
air admission
connection
from below
trough (if applicable)
front
card
cage
mains 1,
mains 2,
load
battery
power cable routing
via the bottom
inverter
stack
inverter
stack
XM136
XM137
Page view 19