APC MGETM GALAXYTM 6000 User Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 46
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
Page 40 - 6739381EN/JD
N
L1
L3
L2
N
L1
L3
L2
Q5N
Q3BP
Q4S
on
off
on
off
on
off
L1 L2 L3N
XF1-XF2
XM1-XM2
K2S
spacing
uprights
card cage
earth strap to be connected
to the front uprights of both
cubicles
Cubicle mounting and connection for 2000kVA Static Switch Cubicle
left cubicle right cubicle
Cubicle mounting
move the cubicles to their operating
location;
adjust the front foot pads so that the
cubicles are vertical and their doors
aligned.
Internal connections between
cubicles
install and bolt the supplied fish-
plates on the bars for the phases and
neutral (L1, L2, L3, N) between the two
cubicles (four bars in top and four bars
in bottom);
connect the earth strap to the front
uprights of both cubicles;
connect the connectors marked XM1
and XM2 from the left cubicle to the
connectors marked XF1 and XF2 in the
right cubicle.