40kW InfraStruXure PDU—Operation and Configuration 29
System Operation
How to Transfer the UPS into Maintenance
Bypass Operation
When servicing the System, transfer the System into maintenance bypass operation. When the
System is operating in maintenance bypass, input power flows directly to the PDU and out to the load
equipment.
Note
Select Help from the top-level menu screen of the PDU display interface and select
the first help topic, Putting the PDU into Maintenance Bypass, or follow the
procedure below.
1. Command the UPS into static bypass operation through the UPS display interface:
a. Press the
E
SC
key at the top-level status screen to
open the top-level menu.
Top-Level Menu
b. Select Control on the top-level menu, and press
the
E
NTER
key.
c. Select UPS Into Bypass on the Control menu
and press the
E
NTER
key.
Control Menu
d. Confirm the selection on the next screen: select
Yes, UPS into Bypass, and press the
E
NTER
key.
Confirmation Screen
Control
Status
Setup
Accessories
Logging
Display
Diags
Help
UPS Into Bypass
Do Self Test
Simulate Power Fail
Graceful Reboot
Graceful Turn Off
Start Runtime Cal
Turn Load On
Confirm
Yes, UPS into Bypass
No, Abort