Web/SNMP Management SmartSlot Card User’s Guide 45
Device Manager Menus
UPS Configuration Options
continued
Shutdown
parameters
Symmetra Power Array, Smart-UPS, and Matrix-UPS use all five
Shutdown Parameter
settings. A Silcon DP300E series UPS uses only
Low-Battery Duration
and
Shutdown Delay
.
Note:
In the Control Console, use the
Configuration
menu’s
Battery
option to access the
Return Battery Capacity
setting.
Continued on next page
Setting Definition
Return Battery
Capacity
The minimum battery capacity that must be present before the
UPS
turns on after a shutdown that was caused by a power
failure.
Note:
The
UPS
must also wait the time defined by the
Return
Delay
setting before it can turn on.
Low-Battery
Duration
How long the
UPS
can continue to run on battery once a low-
battery condition occurs.
Note:
This setting also defines how much time PowerChute
plus has to safely shut down its server in response to
the menu options
Turn UPS Off Gracefully
,
Reboot
Gracefully
, and
Put UPS To Sleep Gracefully
Control
.
Shutdown Delay
How long the
UPS
will wait before it shuts down in response to
a turn-off command.
Return Delay
How long a
UPS
must wait before it turns on after a shutdown
that was caused by a power failure.
Note:
The
UPS
must also have the capacity specified by the
Return Battery Capacity
setting before it can turn on.
Sleep Time
How long the
UPS
will sleep (keep its outlets turned off) when
you use either one of the
Control
menu’s sleep options (
Put
UPS To Sleep
or
Put UPS To Sleep Gracefully
).
Note:
This setting also appears in the “Control” page.