APC AP9606 User's Guide Page 62

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 61
Web/SNMP Management SmartSlot Card User’s Guide 62
Events Menu
Management Card and Device Events
continued
UPS events
The following table identifies all of the UPS events. However, not all of
the events are generated by all UPS models.
Continued on next page
Code Severity Description
0x0101 Informational UPS: Communications established.
0x0102 Severe UPS: Communications lost.
0x0103 Severe UPS: Sensed a load greater than 100 percent of rated
capacity.
0x0104 Informational UPS: Overload condition cleared.
0x0105 Informational UPS: Passed internal self-test.
0x0106 Severe UPS: Failed internal diagnostic self-test.
0x0107 Severe UPS: Batteries discharged.
0x0108 Informational UPS: Battery discharge condition cleared.
0x0109 Warning UPS: Switched to battery backup power; utility power
failure.
0x010A Informational UPS: Returned from battery backup power; utility power
restored.
0x010B Warning UPS: Enabled SmartBoost; low incoming line voltage.
0x010C Informational UPS: Returned from SmartBoost.
0x010D Warning UPS: Enabled SmartTrim; high incoming line voltage.
0x010E Informational UPS: Returned from SmartTrim.
0x010F Severe UPS: Battery power is low and will soon be exhausted.
0x0110 Informational UPS: Returned from a Low-Battery condition.
0x0113 Informational UPS: Turned on.
0x0114 Warning UPS: Turned off.
0x0115 Warning UPS: Entered sleep mode.
0x0116 Informational UPS: Returned from sleep mode.
0x0117 Warning UPS: Started reboot sequence.
0x0119 Severe UPS: Batteries need immediate replacement.
0x011A Informational UPS: Bad battery condition cleared.
0x011B Severe UPS: In bypass due to an internal fault.
0x011C Warning UPS: In bypass due to user command via software or panel.
0x011D Warning UPS: In bypass initiated by user. (The bypass switch at the
UPS was used.)
0x011E Informational UPS: Returned from bypass.
0x011F Severe UPS: Base module bypass power supply failure.
Page view 61
1 2 ... 57 58 59 60 61 62 63 64 65 66 67 ... 83 84

Comments to this Manuals

No comments