APC AP8868 User's Guide Page 41

  • Download
  • Add to my manuals
  • Print
  • Page
    / 104
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 40
Metered Rack PDU User Guide33
devNearOver
Access: Administrator, Device User
Description: Set or view the near-overload threshold in kilowatts for the device.
Example 1: To view the near-overload threshold, type:
apc> devNearOver
E000: Success
20.5 kW
Example 2: To set the near-overload threshold to 21.3 kW, type:
apc> devNearOver 21.3
E000: Success
devOverLoad
Access: Administrator, Device User
Description: Set or view the overload threshold in kilowatts for the device.
Example 1: To view the overload threshold, type:
apc> devOverLoad
E000: Success
25.0 kW
Example 2: To set the overload threshold to 25.5 kW, type:
apc> devOverLoad 25.5
E000: Success
Example 3: To view the overload threshold for guest Rack PDU 3, type:
apc> devOverLoad 3:
E000: Success
5.0 kW
devReading
Access: Administrator, Device User
Description: View the total power in kilowatts or total energy in kilowatt-hours for the device.
Example 1: To view the total power, type:
apc> devReading power
E000: Success
5.2 kW
Example 2: To view the total energy, type:
apc> devReading energy
E000: Success
200.1 kWh
Example 3: To view the total power for guest Rack PDU 3, type:
apc> devReading 3:power
E000: Success
4.2 kW
Argument Definition
power View the total power in kilowatts.
energy View the total energy in kilowatt-hours.
Page view 40