USER’S GUIDE
Switched Rack PDU
31
Control console.
1. Select Phase Management from the Device Manager menu.
2. Select Overload Alarm Threshold (amps), Near Overload Warning Threshold
(amps), or Low Load Warning Threshold (amps).
3. Select Accept Changes.
To set the overload outlet restriction, select Outlet Restriction Configuration on the
Device Manager menu. For 3-phase units, select a phase or bank to display and
change the Outlet Phase/Bank Restriction.
Setting Description
Overload Alarm
Threshold
Set the number of amps that will cause an overload of this phase
or bank.
Near Overload
Warning Threshold
Set the number of amps at which to generate a warning that the
Rack PDU is nearing overload of a phase or bank.
Low Load Warning
Threshold
Set the low threshold, in amps, for the current drawn from this
phase or bank during normal operation. A load below this level
generates a warning, if the load is equal to this threshold, a
warning alarm is not generated.
Overload Outlet
Restriction
Prevent users from applying power to outlets during an overload
condition. You can set the following restrictions for each outlet:
None: You can apply power to outlets regardless of an Overload
Alarm or Near Overload Warning.
On Warning: You cannot apply power to an outlet on the
selected phase or bank if the current for that phase or bank has
exceeded the Near Overload Warning threshold.
On Overload: You cannot apply power to an outlet on the
selected phase or bank if the current for that phase or bank has
exceeded the Overload Alarm threshold.
Coldstart Delay The time that the Switched Rack PDU delays applying power to
the outlets after AC power has been applied to the Rack PDU.