9.Troubleshooting
Problem Possible Cause Solution
The SmartSlot relay I/O
Module does not
respond to control
inputs.
Insufficient setup or
hold times.
Configure controlling
equipment to provide at
least one second of
alarm hold. See
section 4.
Invalid or intermittent
alarms.
Poor contact at either
the dry contact I/O con-
nector or the accessory
connection board.
Correct poor contact
conditions. Tighten all
connector screws.
Alarms always on or
will not come on.
Relay welded.
Return the SmartSlot
Relay I/O module for
service. See section 10.
The SmartSlot Relay I/
O Module does not gen-
erate alarms.
The SmartSlot Relay
I/O Module has failed.
See section 10 for
customer service
information.
Other accessories
attached to the com-
puter interface port of
the UPS stop working.