2. Configuration
Switch setting
The SmartSlot Rela
I/O Module requires confi
uration before test-
in
, final installation, and use. Note: While the SmartSlot Rela
I/O
Module has a four position DIP confi
uration switch (marked CON-
FIG SWITCH on the printed circuit board— see figure 1), onl
posi-
tion 1 is used. The other switches must be left in the off position.
Move the switch up for ON and down for OFF.
Confi
uration 1 is intended for use with UPSs that do not include a
b
pass feature (like Smart-UPS). Confi
uration 2 is intended for use
with UPSs that include a b
pass feature (like Matrix-UPS).
Choose from confi
uration 1 and confi
uration 2 in the table below.
Set CONFIG SWITCH position 1 as required.
Comments to this Manuals