3. Operation Check
Check the operation of the SmartSlot Rela
y
I/O Module before final
installation. Note: The UPS will not protect the load durin
g
this proce-
dure.
1. Check the output relays by temporarily installing the SmartSlot
Relay I/O Module into the SmartSlot. See section 4 for informa-
tion on installing the SmartSlot Relay I/O Module in the Smart-
Slot. Attach the supplied screw terminal connection board.
2. Turn on the UPS. Wait for a few seconds for the SmartSlot Relay
I/O Module to initialize. Use a digital multimeter or continuity
checker to confirm that all N. O. (normally open) output contacts
are open and that all N. C. (normally closed) contacts are shorted.
Measure resistance from each common contact to the correspond-
ing N. O. and N. C. contacts. Short circuit resistance should be
near 0 Ohms, while open circuit resistance should be greater than
1 megaohm.
3. Remove the SmartSlot Relay I/O Module from the SmartSlot and
confirm that all outputs have changed statesthat all N.O. con-
tacts are shorted and that all N. C. contacts are open with respect
to their common contacts.
4. Turn the UPS off. Check the inputs by temporarily installing the
SmartSlot Relay I/O Module into the SmartSlot. Attach the sup-
plied screw terminal connection board.
5. Short circuit input #1 to one of the ground contacts on the screw
terminal connection board. Confirm that the UPS turns on.
Note:
Valid SmartSlot Relay I/O Module inputs require continuous
assertion for at least one second.
6. Short circuit input #2 to ground. Confirm that the UPS turns off.
7. Turn the UPS on and wait for the self-test to complete. Short cir-
cuit input #3 to ground. Confirm that the UPS performs a self-test.
8. Disconnect the UPS from the AC power source. Short circuit
input #4 to ground. Confirm that the UPS enters sleep mode (this
requires from 20 to 600 seconds, depending on internal UPS set-
tings). Reconnect the AC power source to the UPS.