APC SYPM2KU User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 22
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10
For more information about all APC products, go to www.apcc.com
Regional availability: Europe; Middle East; Africa; Asia; Australia; South America
Symmetra Mini-Frame 220; 230; 240 VAC (Output) Symmetra Master Frame 220; 230; 240 VAC (Output)
System Part No. Single phase in/out (1:1) SY4KEXI SY8KI SY8KEXI SY12KEXI SY16KI
3-phase in/single phase out (3:1) n/a n/a SY8KEX3I SY12KEX3I SY16K3I
Output
Capacity 4kVA/2.8kW 8kVA/5.6kW 8kVA/5.6kW 12kVA/8.4kW 16kVA/11.2kW
Output Voltage 220; 230; 240
Max Configurable Power
with additional Power Modules 8kVA/5.6kW 16kVA/11.2kW
Output Connections (1) hardwire plus (8) IEC 320 C13
Efficiency at full load 91%
By pass Internal Bypass (Automatic&Manual)
Output voltage Distortion typically <5% at full load (linear or non-linear)
Output frequency (synched to mains) 47-63 Hz
Output frequency (not synched) 60; 50 Hz
Crest Factor up to 5:1
Input
Nominal input Voltage (1:1) 220; 230; 240
Nominal input Voltage (3:1) n/a n/a 380; 400; 415V (3-phase)
Input Frequency 50/60Hz +/-5 Hz (auto-sensing)
Input Connection Hardwire (3-wire) Hardwire (3-wire) (5-wire for 3:1 unit)
Input Voltage range (1:1) 155-276 V at 100% load
Input Voltage range (3:1) n/a n/a 290-480V
Input Power Factor at full load 0.98 0.98 (.95 for the 3:1)
Batteries
Battery Type Maintenance-free, sealed lead-acidbattery with suspended electrolyte; leakproof.
Typical recharge time <3 hours
Replacement Battery Module (1) SYBATT (2) SYBATT (2) SYBATT (3) SYBATT (4) SYBATT
Communications and Management
Interface port DB-9; RS-232; Smart-Slot Card (4)
Management Software included PowerChute Network Shutdown;Web/SNMP Management Card built into unit
Control panel Multi-function LCD status & control console in multiple languages
Audible Alarm Alarm when on battery; distinctive low battery alarm; configurable delays
Emergency Power Off (EPO) Yes
Physical
Dimensions HxWxD (in/cm) 1:1 33x24x27in /84x61x69cm 47.2x24x27in/120x61x69cm
Weight net (lbs/kg) 1:1 273lb/124kg 367lb/167kg 431lbs/196kg 526lbs/239kg 620lb/282kg
Weight shipping 1:1 363lb/166.5kg 477/217kg 543lbs/247kg 654.5lbs/297.5kg 765.6lb/348kg
Dimensions HxWxD (in/cm) 3:1 n/a n/a 45x24x27in/120x61x77cm
Weight net (lbs/kg) 3:1 n/a n/a 439lbs/199.5kg 533.5lbs/242.5kg 628lb/285.5kg
Weight shipping 3:1 n/a n/a 557lbs/253kg 667.7lbs/303.5kg 779lb/354kg
Environmental
Operating Temperature 0-40 C/ 32-104 F
Operating Relative humidity 0-95%
Operating Elevation 0-10000 feet/ 0-3000m
Storage Temperature -15 to 45C/ 5 to 113F
Storage Relative Humidity 0-95%
Storage Elevation 0-50,000 feet/0-15,000m
Audible noise at 3 feet (1 m) 62dBA
On-line thermal dissipation (BTU/hr) 945 1890 1890 2834 3779
Conformance
Approvals C-tick; CE: EN 50091-2; VDE
Warranty & Service Options
Warranty 2 year; repair or replace (1 year for Battery Modules in India)
“T” level for Service Option pricing T8 T8 T9 T9 T9