Unit Load Standard Plus (1). Plus (1) Plus (1) Plus (1) Plus (1)
(kVA/kW) Configuration SYXR2B4 SYXR4B4 SYXR4B12 SYXR8B12 SYXR12B12
4kVA 2/1.4 15 m 70 m 2.1 hr 2.1 hr 4.3 hr 7 hr
Scalable to 8kVA 4/2.8 6 m 27 m 53 m 53 m 1.9 hr 2.9 hr
8kVA 2/1.4 40 m 1.6 hr 2.7 hr 2.7 hr 4.8 hr 6.4 hr
4/2.8 15 m 40 m 1.1 hr 1.1 hr 2.1 hr 3.1 hr
6/4.2 9 m 23 m 40 m 40 m 1.3 hr 1.9 hr
8/5.6 6 m 15 m 27 m 27 m 53 m 1.4 hr
8kVA Scalable 4/2.8 15 m 40 m 1.1 hr 1.1 hr 2.1 hr 3.1 hr
to 16kVA 6/4.2 9 m 23 m 40 m 40 m 1.3 hr 1.9 hr
8/5.6 6 m 15 m 27 m 27 m 53 m 1.4 hr
12kVA Scalable 4/2.8 27 m 53 m 1.4 hr 1.4 hr 2.3 hr 3.4 hr
to 16kVA 6/4.2 15 m 31 m 49 m 49 m 1.5 hr 2.1 hr
8/5.6 10m 21 m 33 m 33 m 1 hr 1.5 hr
10/7 7m 15 m 25 m 25 m 46 m 1.1 hr
12/8.4 6m 12 m 19 m 19 m 35 m 53 m
16kVA 8/5.6 15m 27 m 40 m 40 m 1.1 hr 1.7 hr
10/7 11m 20 m 29 m 29 m 51 m 1.3 hr
12/8.4 9m 15 m 23 m 23 m 40 m 1 hr
14/9.8 7m 12 m 18 m 18 m 32 m 48 m
16/11.2 6m 10 m 15 m 15 m 27 m 39 m
Step 4
Determine runtime
requirement for
Symmetra Tower.
Number of Battery Modules and Intelligent Extended Battery Cabinets required for extended runtimes
Proceed to Step 5
(next page.)
SYBATT SYBATT
SYBATT
SYBATT
4-Bay Intelligent
External Battery Cabinets
4-Bay Cabinet Specifications:
Dimensions:
19.3x24x27” (49x61x69cm)
Weights: (fully configured)
Net: 324lb/147.3kg Shipping: 384lb/174.5kg
12-Bay Cabinet Specifications:
Dimensions:
47x24x27” (126x61x69cm)
Weights: (fully configured)
Net: 944lb/429.5kg Shipping: 1055lb/479.5kg
System Part #
SYXR2B4
1
, SYXR2B4I
2
, SYXR2B4J
3
System Part #
SYXR4B4
1
, SYXR4B4I
2
, SYXR4B4J
3
Optional Step for Tower Units - add additional runtime
with Intelligent External Battery Cabinets
1
-For use with systems on page 9
2
-For use with systems on page 10
3
-For use with systems on page 11
Unit Load Standard Plus (1) Plus (2) Plus (3) plus (4) plus (5) plus (1) Plus (1)
(kVA/kW) Configuration SYBT2 SYBT2 SYBT2 SYBT2 SYBT2 SYRMXR SYRMXR
* * * * * 2B4 4B4
2kVA Scalable to 6kVA 2/1.4 10 m 26 m 47 m 1.1 hr 1.5 hr 1.9 hr 2.6 hr 3.6 hr
4kVA Scalable to 6kVA 2/1.4 26 m 47 m 1.1 hr 1.5 hr n/a n/a 2.2 hr 3 hr
4/2.8 10 m 18 m 28 m 39 m n/a n/a 1 hr 1.4 hr
6kVA 2/1.4 47 m 1.1 hr n/a n/a n/a n/a 1.9 hr 2.6 hr
4/2.8 18 m 28 m n/a n/a n/a n/a 50 m 1.2 hr
6/4.2 11 m 16 m n/a n/a n/a n/a 29 m 44 m
*Note: SYBT2 Battery modules can be used in any open bay for maximum runtimes
Unit Load Standard Plus (1) Plus (1) Plus (1) plus (1) plus (1) plus (2)
(kVA/kW) Configuration
SYBT3 SYXR2B4 SYXR4B4 SYXR8B12 SYXR12B12 SYXR12B12
8kVA Scalable to 12kVA 4/2.8 15 m 27 m 53 m 1.4 hr 2.3 hr 3.4 hr 7.6 hr
(N+1) or 16kVA (N) 6/4.2 9 m 15 m 31 m 49 m 1.4 hr 2.1 hr 4.3 hr
8/5.6 6 m 10 m 21 m 33 m 1 hr 1.5 hr 3.1 hr
12kVA Scalable to 12kVA 4/2.8 27 m n/a 53 m 1.4 hr 2.3 hr 3.4 hr 7.6 hr
(N+1)or 16 KVA (N) 8/5.6 10 m n/a 21 m 33 m 1 hr 1.5 hr 3.1 hr
12/8.4 6 m n/a 12 m 19 m 35 m 53 m 1.9 hr
Proceed to Step 5 (next page.)