Chapter 3. UPS configurations for cluster 53
Figure 52. Two UPS units without application handling
But connecting the power cords in this way prevents correct application handling.
Communication is possible only between one server and one UPS. Therefore, if a
server receives a UPS signal, software on this server cannot check the power
status of the second UPS. For example, phase B fails. Server 2 gets the signal
from UPS 2. Should server 2 begin to shut down? For this decision, information
about UPS 1 would be needed but is not available. Even if server 2 always
decides for shutdown, a question would remain about bringing the applications
offline or moving them to server 1.
This solution is appropriate when application handling is not required and the
focus is on redundant power. An example is a file server cluster; losing power
without executing an ordered shutdown is a risk for data consistency.
Figure 53 shows better cabling, which we recommend for correct UPS
communication.
Cluster
UPS 1
Phase A
Phase B
Server 1
UPS 2
Server 2
Communications - smart-signaling cable
Communications - smart-signaling cable