16 APC NetworkAIR CM Series: Performance Specifications
Net cooling capacitywater
MODEL
CAPACITY IN BTU/H 1T 1.5T 2T 3T 4T 5T
80° F DB, 67° F WB Total (BTUH) 16,300 21,400 25,600 43,300 54,600 62,600
(26.7° C DB, 19.4° C WB) (kW) (4.8) (6.3) (7.5) (12.7) (16.0) (18.3)
50% RH Sensible (BTUH) 13,200 16,000 20,200 36,500 43,500 49,700
(kW) (3.9) (4.7) (5.9) (8.4) (12.7) (14.6)
75° F DB, 62.5° F WB Total (BTUH) 15,000 19,700 23,800 34,000 50,700 58,200
(26.7° C DB, 19.4° C WB (kW) (4.4) (5.8) (7.0) (10.0) (14.8) (17.0)
50% RH Sensible (BTUH) 13,000 15,800 19,900 27,300 43,000 49,200
(kW) (3.8) (4.6) (5.8) (8.0) (12.6) (14.4)
75° F DB, 61° F WB Total (BTUH) 14,700 19,400 23,300 33,400 50,000 57,400
(23.9° C DB, 16.1° C WB) (kW) (4.3) (5.7) (6.8) (9.8) (14.6) (16.8)
45% RH Sensible (BTUH) 14,000 17,000 21,200 29,000 46,200 52,800
(kW) (4.1) (5.0) (6.2) (8.5) (13.5) (15.5)
72° F DB, 60° F WB Total (BTUH) 14,300 18,900 22,800 32,600 48,700 55,800
(22.2° C DB, 15.5° C WB) (kW) (4.2) (5.5) (6.7) (9.5) (14.3) (16.3)
50% RH Sensible (BTUH) 12,600 15,500 19,400 26,700 42,100 48,200
(kW) (3.7) (4.5) (5.7) (7.8) (12.3) (14.1)
72° F DB, 58.6° F WB Total (BTUH) 14,100 18,600 22,400 32,200 49,500 55,200
(22.2° C DB, 14.8° C WB) (kW) (4.1) (5.4) (6.6) (9.4) (14.5) (16.2)
45% RH Sensible (BTUH) 13,600 16,500 20,700 28,500 48,500 51,700
(kW) (4.0) (4.8) (6.1) (8.3) (14.2) (15.1)
70° F DB, 58.5° F WB Total (BTUH) 13,800 18,300 22,100 31,700 48,500 54,300
(22.1° C DB, 14.8° C WB) (kW) (4.0) (5.4) (6.5) (9.3) (14.2) (15.9)
50% RH Sensible (BTUH) 12,400 15,200 19,100 26,300 44,600 47,300
(kW) (3.6) (4.5) (5.6) (7.7) (13.1) (13.8)
70° F DB, 57.2° F WB Total (BTUH) 13,600 18,100 21,800 31,200 48,200 53,800
(22.1° C DB, 14.8° C WB) (kW) (4.0) (5.3) (6.4) (9.1) (14.1) (15.8)
45% RH Sensible (BTUH) 13,200 16,200 20,200 27,700 47,400 50,600
(kW) (3.9) (4.7) (5.9) (8.1) (13.9) (14.8)
* Performance Specifications @ 95° F Ambient (AIR/GLYCOL/RC) or @ 105° F Condensing (WATER)