30 APC NetworkAIR CM Series: Guide Specifications
Air distribution and air pattern. The evaporator airflow pattern shall be
________ (spot-cooler or ducted). The spot-cooler configuration shall be
supplied with a 2 × 4 (610 mm × 1220 mm) supply/return air filter
assembly. The filter assembly shall include one-way supply and return air
grilles with a 20" × 20" × 1" (508 mm × 508 mm × 25 mm) 30% efficient
ASHRAE 52.1-92 return air filter. The ducted configuration shall be supplied
with 1" (25 mm) duct flanges on the supply and return air openings. A 20" ×
20" × 1" (508 mm × 508 mm × 25 mm) 30% efficient ASHRAE 52.1-92
return air filter shall be integrally mounted on all CM15 throughCM40
systems. Two 16" × 25" × 1" (406 mm × 635 mm × 25 mm) 30% efficient
ASHRAE 52.1-92 return air filters shall be integrally mounted on all CM50
through CM65 systems. The air distribution system for the CM15 through
CM40 shall be comprised of a direct-drive fan motor with a double-inlet
blower and permanently sealed ball-bearing type blower bearings. The air
distribution system for the CM50 through CM65 shall be comprised of a belt
drive fan motor with a double-inlet blower and permanently sealed ball-
bearing type blower bearings.
High efficiency filter (ducted applications only). A _______% efficient
_______ in. (_______ mm) ASHRAE 52.1-92 return air filter shall be
supplied in-lieu-of the standard filter.
Bi-metallic thermostat/humidity controls. The system shall be supplied
with a wall-mounted bi-metallic thermostat for temperature control. The
thermostat shall have an external lever and scale for temperature setting.
When equipped with a humidifier and/or reheat, a hair-element humidistat
and/or dehumidistat shall be supplied to control humidification and/or
dehumidification.
Compressor short-cycle controls. The control system shall prevent
excessive compressor cycling.
Remote on/off control. A terminal board jumper connection shall be
provided for remote on/off control.
Direct Expansion
Systems
DX (Direct Expansion) coil. The evaporator coil shall be constructed of
copper tubes and aluminum fins and be mounted in a stainless steel
condensate drain pan. The drain pan shall be equipped with dual condensate
overflow safety switches. The coil shall have a minimum face area of
_______ ft² (______ m²) and be ______ rows deep. The maximum coil face
velocity shall be _______ ft/m (_______ m/s) at ______ CFM (_______ L/s).
Air-cooled with close-coupled or remote indoor centrifugal con-
denser.
The evaporator section and condenser section shall be factory
assembled and ship as one-piece. The system shall be pre-charged with
refrigerant an require no inter-connecting piping or brazing. The refrigeration
system shall consist of hermetic compressor with vibration isolators, high
pressure switch, filter/drier, sight glass, and externally equalized expansion
valve. The condenser section shall be equipped with 1" (25mm) duct flanges
for inlet and discharge ducting. The coil shall be constructed of copper tubes
and aluminum fins. The centrifugal condenser fan shall deliver ______ CFM
(______ L/S) at ______ in. wg. (______ Pa). For the CM15 through CM40,
the condenser fan shall cycle from high speed to low speed based on entering
condenser air temperature. The condenser section shall be sized to provide