APC NetworkAIR CM Series: Guide Specifications 29
Guide Specifications
General Summary. These specifications described herein are for an environmental
control system. The system shall be designed specifically to monitor and
control temperature and relative humidity within a conditioned space. The
manufacturer shall supply all equipment in the quantities and configurations
shown on the project drawings. The system shall be NRTL listed.
Design requirements. The system shall be as described in the following
specification as manufactured by APC.
Model AFX _____________________________________.
Total cooling capacity: ________________ MBH (kW).
Sensible cooling capacity: ________________ MBH (kW).
Return air temperature: ________________ ° F (° C).
Dry bulb: ________________ ° F (° C).
Wet bulb: ________________% RH.
Air quantity: ________________ CFM (L/s) at 0.5" (125 Pa) external static
pressure.
Humidifier capacity: ________________ kW.
Electrical supply: __________ V, ______ ph, 60 Hz.
Submittals. Submittals shall be provided with the proposal and shall
include: Capacity data, electrical data, physical data, electrical connection
drawing, piping connection drawing, and electrical wiring schematic.
Quality assurance. The system shall be completely factory-tested prior to
shipment. Testing shall include, but not be limited to; Completely charging
the system (where applicable) with refrigerant to ensure pressurized integrity,
Hi-Pot test, and controls calibration/setting. Each system shall ship with a
completed test report to verify completion of factory-testing procedure.
Product Unit construction. The chassis and access panels shall be constructed of
heavy gauge galvanized. Hanger mounting brackets shall be part of the
chassis and shock-mounts shall be provided for vibration isolation. Access
panels shall be insulated with 1/2" (12mm) thick 1½ lb./ft² (24kg/m²).