20 kVA - 80 kVA UPS
Users and Installation Manual
1015543
Revision D
7
Efficiency Optimizer
In addition to the traditional on-line operation mode this UPS features the Efficiency Optimizer
function - a new feature adding real cost effectiveness to the UPS. It minimises the power loss
and reduces power consumption. The UPS automatically switches between bypass and on-line
mode according to the utility power condition. Whenever there are imperfections in the mains
supply the UPS feeds power in on-line mode. When mains power is smooth and free from
disturbances the UPS switches automatically to bypass mode for maximum efficiency. If needed,
UPS detects all mains imperfections in a fraction of a second and turns back to on-line mode. As
a result the UPS reaches up to 98% average efficiency. The Efficiency Optimizer function is
standard in this UPS and can easily be activated via the serial interface port during initial start up
by the service engineer. The UPS can of course run permanently in traditional on-line mode if
prefered. All models of 20 - 80 kVA UPSs run in the traditional on-line mode as default.
2.2 System configuration
The UPS system consists of the UPS device itself and the external backup battery. In
addition, several options may be included in the system. The options are used to tailor a
matching solution to fulfil the site and load requirements of the installation.
The main considerations in planning the UPS system are:
The UPS output power rating (VA) shall be specified according to the total power demand of
the protected system. Some margin should be allowed for potential expansion of the
protected system, and for possible inaccuracy in calculating or measuring the actual power
requirement.
The battery shall be sized according to the desired backup time. Note that the backup
time is longer if the load is less than the nominal power rating of the UPS.
The following options are available:
Output isolation transformer
10% input filter (THDI)
External battery cabinets
Remote display unit (ViewUPS)
Alarm extension unit
LanQuattro
Connect UPS (SNMP adapter)
Table 1. describes UPS equipment backup times of battery options related to the UPS ratings.
Table 1.
The backup times are for standard batteries and long life batteries.
The backup times indicated in parentheses are for units with battery banks of 32 pcs battery
system.
See the dimensions of the UPS series and different battery options in figure 2.
rewoptuptuOSPUseirettaBlanretnIDTABETABFTABETABx2
Wk41/AVk02SPUnim)7(21nim52nim54nim09nim011
Wk12/AVk03SPUnim7nim51nim82nim55nim56
Wk82/AVk04SPU- nim01nim91nim53nim54
Wk53/AVk05SPU- nim7nim31nim52nim53
Wk24/AVk06SPU--nim01nim02nim82
Wk65/AVk08SPU---nim11nim51