ReturntoNormalOperation,ParallelUPSWithExternalBypassCabinet
1.CheckthatallswitchesontheUPSsaresetto
OFF.
2.ApplybypassandinputpowertoUPSs.
3.SetswitchQ4S(B)oneachUPStoON.
4.SetoutputswitchQ5N(D)oneachUPSand
CB11–16,asapplicable,toON.
5.CheckthatalltheUPSspresentinthe
installationareincludedinthelistonthedisplay
andconrmbypressingthefunctionkeyon
eachUPS.
6.SetCB2intheexternalsystembypasscabinet
toON.
7.SetCB1intheexternalsystembypasscabinet
toOFF.
8.SettheinputswitchQ1(A)oneachUPSunit
toON.
9.Setthebatterycircuitbreakersoftheauxiliary
cabinetstoON.
TheUPSunitsstartautomatically.LED(E)
isON.TheloadisprotectedbytheUPS.
IftheLED(E)remainsOFF,presstheON
button(H)oneachUPSunit(theUPSisin
manualstartmode)andconrm,ifnecessary,by
pressingthefunctionkeymarked←.
IftheLED(E)stillremainsOFFandeitherof
theLEDs(F)or(G)isON,afaulthasoccurred
(see“IdenticationofAlarms“).
990-5219-001
MGEGalaxy500040-130kV A480V
21