31
5.0 Operation
5.2.3 UPS Control menu
The UPS Control menu allows the user to access sub-menus that show UPS switch
on/off and bypass in/out operation choices. To avoid accidentally powering or
unpowering the load when a UPS on/off control choice is mistakenly entered, the
UPS will ask the user to confirm the choice.
5.2.4 UPS Status menu
The UPS Status menu allows the user to access sub-menus that show UPS, Battery
Pack, mains, and load parameter values. These parameters are described below.
This screen shows the true rms input line voltage. The
accuracy of this measurement is ±5% of the full scale
value of 285 Vac.
This screen shows the UPSs true rms line-line output
voltage. The accuracy of this measurement is ±5% of the
full scale value of 285 Vac.
This screen shows the applied load as a percentage of the
UPS's full rated capacity. The accuracy of this measure-
ment is ±4% of the full scale value of 105%.
This screen shows the estimated run time available in
minutes. The indication is based on available battery
capacity and the applied load. The UPS keeps track of
changing battery performance and adjusts the available
run time indicated for weak batteries nearing the end of
their service life.
This screen shows the internal temperature of the
Electronics Unit in degrees Centigrade. The indicated
temperature rises when the UPS is operating on-battery
and when the ambient temperature rises.
This screen shows the available battery capacity as a
percent of the fully charged condition.