13Smart-UPS X-Series Operation
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in
the factory. These settings can only be modified using an external interface, like the NMC web interface.
• NMC IP Address Mode
• NMC IP Address
• NMC Subnet Mask
• NMC Default Gateway
Load Shed On
Runtime
Disabled • Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with
delay
•Disabled
When the battery runtime falls below the
specified value, the Controllable Outlet Group
will turn off.
Configure this time using the
LOAD SHED
R
UNTIME REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level,
the Controllable Outlet Group will turn off.
Load Shed on
Overload
Disabled • Disabled
• Enabled
In the event of an overload (greater than 100%
output), the Controllable Outlet Group will
immediately turn off to conserve power for
critical loads. The Controllable Outlet Group
will only turn on again with a manual
command.
Function Factory Default Options Description
Comments to this Manuals