APC ACECFR20200SE4 Installation Manual Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 60
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
EcoBreeze System Operation and Maintenance26
Water Service. (Requires admin password)
Setpoint: 500 - 15000 uS/cm
Deadband: 25 - 15000 uS/cm
Conductivity Min/Max: Select the range that corresponds to the selection made on the
conductivity sensor.
– 500 - 2500 uS/cm
– 2500 - 15000 uS/cm
ServiceCmplt: No/Yes - Select Yes to clear the Water Treatment System Maintenance
Required alarm and to set the Last Service date to the current date.
Last Service: 01/01/2001- Displays the last time the water treatment system was
serviced.
The Setpoint setting will be in the highlighted box on the screen. Use the
DOWN key to move
the highlight box to your selection and press
ENTER to select it. Press ENTER to cause the box to
flash. Then press the
UP OR DOWN keys to change the setting. Press ENTER to save your change.
Press
ESC to return to the previous screen. The Last Service setting cannot be changed from
this screen.
Discrete I/O Setup. (Requires admin password)
Digital I/O Normal States: Sets the normal state of the contact (Open or Closed). The
input/output will become active when its state is opposite the normal state.
– Remote Run/Stop: Open
– Isolation Damper: Open
Alarm Contact: Open
The Remote Run/Stop setting will be in the highlighted box on the screen. Use the
DOWN key
key to move the highlight box to your selection and press
ENTER to select it. Press ENTER to
cause the box to flash. Then press the
UP or DOWN keys to change the setting. Press ENTER to
save your change. Press
ESC to return to the previous screen.
Map Alarms. (Requires admin password)
Choose to have the system announce all alarms or only critical alarms.
Activate Alarm Relay on:
Any Alarm / Critical Alarm
The current choice will be in the highlighted box when the screen opens. Use the
UP or DOWN
keys to change the setting. Press
ENTER to save the change. Press ESC to return to the previous
screen.
Page view 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 59 60

Comments to this Manuals

No comments