General cleaning
Inspect and clean the EcoBreeze system on a regular basis. Do not use cleaners, chemicals,
or other materials with strong fumes or odors. Thoroughly remove all cleaning solution residue
from interior surfaces.
Remove any debris.
Exterior: Spray wash the exterior with low pressure water and a mild detergent. All
detergent must be removed with clean water.
Coils (evaporative and condenser): Clean the fins with steam or a non-corrosive solvent
and water hose to remove oil, pollen, dust, and soil. Do not use a direct high-pressure
blast as damage to the coil may occur. Do not spray water into any compartment not
equipped with a floor drain. Excessive accumulations of water could leak or cause
damage.
Dump and flush the basin. Ensure the fill line drain valve opens when the fill valve closes
and that the basin drain opens.