EcoBreeze System Operation and Maintenance40
Module alarms
• “COMPRESSOR ALARMS” on page 40
• “ELECTRONIC EXPANSION VALVE (EEV) ALARMS” on page 40
• “FAN ALARMS” on page 41
• “POWER ALARMS” on page 41
• “REFRIGERATION SYSTEM ALARMS” on page 41
• “TEMPERATURE/HUMIDITY ALARMS” on page 42
• “WATER SYSTEM ALARMS” on page 43
• “VARIABLE FREQUENCY DRIVE (VFD) ALARMS” on page 43
Name Severity Alarm Actions
COMPRESSOR ALARMS
Compressor Start Failed Critical • Check the power supply.
• Check the wiring and connections.
• Check the motor protection device.
• Check the temperature of the compressor.
• Check the refrigerant charge.
• Check expansion valve.
• Check the drive configuration.
• Replace the compressor if necessary.
Compressor Overcurrent Fault Critical • Check the refrigerant charge.
• Check the power supply.
• Check the wiring and connections.
• Check the motor protection device.
• Check the temperature of the compressor
• Replace the compressor if necessary.
Compressor Impending Short-
circuit Fault
Warning • Check the compressor wiring.
• Replace the compressor if necessary.
Compressor Short to Earth Critical • Check the compressor wiring.
• Replace the compressor if necessary.
Compressor Phase to Phase
Short
Critical • Check the compressor wiring.
• Replace the compressor if necessary.
ELECTRONIC EXPANSION VALVE (EEV) ALARMS
EEV Communication Fault Critical Check the communications cabling and power to the device.
Low Superheat Warning • Check the suction pressure transducer reading.
• Check the suction temperature sensor reading.
• Check operation of the EEV.
• Check the refrigerant charge.
High Superheat Warning • Check the suction pressure transducer reading.
• Check the suction temperature sensor reading.
• Check operation of the EEV.
• Check the refrigerant charge.
EEV Pressure Sensor Fault Critical • Check the suction pressure transducer reading.
• Check the suction temperature sensor reading.
• Check operation of the EEV.
• Replace the sensor.