EcoBreeze System Operation and Maintenance44
Troubleshooting
NOTE: The EcoBreeze operates using controllers to control internal functions along with variable
frequency drives (VFDs). If either detects a problem, it will go into an alarm mode. Refer to the
remote display panel active alarms and status screens for additional help.
Problem Possible Cause Corrective Action
Module # will not
run
No power
• Module address not configured
Check that the disconnect switch on the Module
control panel has not been shut off.
Check Module address configuration.
Basin has
excessive
sediment
Conductivity setting requires
adjustment
Basin drain is blocked by dirt
or debris
Consult the water treatment specialist for
alternate conductivity settings.
Check the basin drain for blockage.
Check for open areas of the basin. Replace basin
covers.
Scale buildup on
heat exchangers.
Conductivity setting requires
adjustment.
Consult the water treatment specialist for
alternate conductivity settings.
Water spray
system pump will
not run
Pump is not receiving power
Water level is too low
Pump motor protection device
is tripped
Pump is shut off and the basin
is empty. (The ambient
temperature is below 4.4°C
(40°F).)
Check the power supply, then the pump
contactor.
• Check that the fill, fill vent, and basin drain valves
are working properly.
Reset the pump motor.
No action required. System is working properly.
Water spray
system pump runs
but spray does not
cover the heat
exchanger
Strainer clogged.
Spray nozzle obstruction
Clean the strainer.
Clean the spray nozzle.
VFD protection
trips
VFD fault Check the fault code on the VFD. Refer to the
VFD manual for more information.
Airflow too low Supply airflow restriction
Air filters are clogged
Check the return and supply air damper
positions.
Replace air filters.
Evaporator coil
ices
• Dirty or blocked evaporator coil
Air filters are clogged
Low IT air flow rate and low
refrigerant charge
Clean the evaporator coil.
Replace the air filters.
Check operation of the IT fans
Check the refrigerant charge
Compressor fails
to start
VFD fault
No power to the compressor
• Minimum Off delay timer active
Another Critical Alarm is active
Check the fault code on the VFD.
Check the power supply to the compressor.
Wait for the minimum Off time to expire.
Check for other critical alarms.
Head pressure too
high
Air cooled condenser
malfunction
Erroneous sensor reading
Check and clean the condenser coil. Check the
OA fan operation and settings.
Check the pressure and temperature sensors.
Head pressure too
low
Low refrigerant charge
Erroneous sensor reading
Check for proper subcooling. Repair any leak
and recharge the system.
Check the OA fan operation during low ambient
temperature.
Check the pressure and temperature sensors.