EcoBreeze System Operation and Maintenance28
View Setup. Press the UP or DOWN keys to view all sensor information being collected by the
Frame controllers. No password is required to view this screen.
• Supply Air Setpt: 75.0°F/°C
• Contain Setpt: 100.0 Pa
• Fan Speed: 0%
• Conduct Setpt: 2500 uS/cm
• Conduct Dedbnd: 1000uS/cm
• Lead Pump: A
• Pri (Primary) Water Src: A
• IT Fan Mode: Auto
• Elevation: ftx10/mx10
• Damper Present: No
• Contain Gain: 0.000%/Pa
• Contain Reset: 0.0011 sec
• DP Sensor Select: None
• DP Sensor Min: 0.0 Pa
• DP Sensor Max: 0.0 Pa
• Pump Rot Intvl: 2 Days
• Water Saver: On/Off
• Dry Op Delay: 24 hrs
• Conduct: Range - 500-2500 uS/cm
• Remote Run/Stop: N.O.
• Isolation Damper: N.O.
• Alarm Contact: N.O.
• AFC HACS/CACS Sel: HACS
• AFC Setpoint: Zero
• Number of AFCs: 0
• Enable Lamp Test: No
• AFC Modbus ID: 0
• AFC Altitude: 0m