InfraStruXure InRow RC—Operation and Maintenance 7
Set Up Contacts
Input/output contacts
Path: Main > Configure Unit > Discrete I/O
Each cooling unit supports a user-defined input contact and a user-defined output contact. Each
contact monitors a sensor and responds to changes in the state of the sensor (open or closed).
Input State. Indicates the actual state of the input contact (open or closed). A cooling unit is On
when the state is normal, and in Standby when the state is not normal.
Output State. Indicates the actual state of the output contact (open or closed). An alarm will cause
the output contact to change from the normal state.
Normal State. Edit the input and output contact normal states.
You can set input contacts to cause alarm conditions based on a user-defined normal state. Output
contacts can map internal alarms and events to outside devices.
Path: Main > Configure Unit > Discrete I/O > Normal State
Input Normal.
Choose the normal state of the contact. The cooling unit changes its operating mode
to Standby when the normal state differs from the actual state.
Output Normal. Set the normal state for this contact. If the state of an alarm or event mapped to this
contact changes from the normal state, the contact also changes state.
Output Source. Define the type of alarm, either Any Alarm or Critical, that causes the output to
change from its normal state.
Input State: Open
Output State: Open
Normal State
na1651a
Input Norm: Open
Output Norm: Open
Outpt Src: Any Alrm
na1652a
Input Norm: Open
Output Norm: Open
Outpt Src: Any Alrm
na1652a