2 InfraStruXure InRow RC—Operation and Maintenance
Using the Display
Every time you apply power to the APC
®
InfraStruXure
®
InRow RC, the display initializes and runs
an LED and alarm-tone test.
Scrolling status screens
After start-up, the interface displays the firmware revision number of the display interface.The
display interface then scrolls automatically and continuously through screens of status information.
Press the up or down arrow key to interrupt the automatic scrolling and view a specific status screen.
Press ESC to switch to the main menu. Scrolling automatically resumes five seconds after no key
activity.
Status Screen Name Status Information Displayed
APC InfraStruXure
InRow RC Status
(APC ACRC)
• On/Standby
• Unit identifier
• Cooling unit name
• Cooling unit location
Cooling Group • Alarms/No Alarms
• Cool Output kW
• Cool Setpoint °F (or °C)
• Maximum Rack temperature °F (or °C)
Cooling Unit • Alarms/No Alarms
• Cool Output kW
• Rack Inlet °C (or °F)
• Air Flow CFM (cubic feet per minute) or L/s (liters per second)