Operation: Control the Environment
InfraStruXure InRow RC—Operation and Maintenance 11
Fan Spd. Set the fan speed preference for the cooling group. Each fan speed provides an approximate
temperature difference (DT) between the supply air from the InRow RC and the air returned from the
rack.
Low=30°F (16.7°C) DT
Med-Low=25°F (13.9°C) DT
Med=20°F (11.1°C) DT
Med-High=15°F (6.3°C) DT
High=10°F (5.6°C) DT
PID settings
Path: Main > Set Group PID
The Proportional plus Integral plus Derivative (PID) loop is used to
control the output of the cooling group.
Gain (P). The proportional multiplier (gain) for this mode or actuator.
The proportional multiplier adjusts for the difference (error) between
the measured temperature and the setpoint. The proportional multiplier
is expressed in percent of output per unit error.
Rate (I). The integral multiplier (reset rate) for this mode or actuator.
The integral multiplier adjusts for error measurement, and the amount
of time that the error has existed. The integral multiplier adds to or
subtracts from the output in small increments to correct for the offset
error caused by the proportional contribution. It is expressed in percent of output for each minute and unit
of error (error multiplied by minutes).
Deriv (D). The derivative multiplier (derivative) for this mode or actuator. The derivative multiplier
adjusts the output for rapid changes in the error, correcting for the rate of change of the error over time. It
is expressed in percent of output for each unit of error per minute (error divided by minutes).
Note
The cooling group will automatically override this fan speed setting and adjust the fan
speed to provide optimum cooling for the rack as needed.
The PID settings apply only when using the In-Row rack
deployment strategy. See “Configure the cooling group” on
page 8 for information on selecting a rack deployment
strategy.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1638a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds
Cool
Gain(P): 20
Rate(I): 0
Deriv(D): 0
.00
.00
.00
na1653a