10 InfraStruXure InRow RC—Operation and Maintenance
Control the Environment
The InRow RC utilizes a chilled water coil, a valve to modulate fluid flow through the chilled water
coil, and a set of fans to control airflow through the coil. The control strategies employed depend
upon the deployment strategy of the cooling group.
In an In-Row environment, the InRow RC supplies constant-temperature supply air to the common
cold aisle. The fan speed is modulated to ensure that the desired volume of air reaches the IT
equipment.
In a HACS or RACS environment, the InRow RC neutralizes the heat accumulated in the common
hot aisle and expels it back into the environment after the heat is neutralized while maintaining the
desired temperature gradient across the group.
Setpoints
Path: Main > Set Group Setpoints
A setpoint is the target value that a cooling group will maintain in
the rack. The default setpoints are appropriate for most cooling
applications.
Cool. Set the temperature that the cooling group should maintain
if you have chosen the In-Row rack deployment strategy. The
setpoint must be within 60.8–77.0°F (16.0–25.0°C).
Supply Air. The setpoint must be within 32.0–73.4°F
(0.0–23.0°C).
For an In-Row rack deployment strategy, the desired
temperature of the common cold aisle.
For a HACS or RACS deployment strategy, the desired
temperature of the air expelled into the surrounding
environment.
Note
The Supply Air setting is defined by the field service representative when the cooling
group is commissioned.
On/Standby
View Alarms
Clear Alarms
View Event Log
na1637a
Clear Event Log
Configure Modbus
Set Date & Time
Set Password
Set Display Units
Configure Display
Configure Network
About InRow RC
Set Identification
Service Intervals
View Run Hours
Configure Unit
Configure Group
Set Group PID
View Group Status
View Unit Status
Set Group Setpoints
Set Unit Thresholds
Cool: 72.3 F
Supply Air: 71.2
Fan Spd: Med High
°
°
F
na1656a